
20
INSTALLATION INSTRUCTIONS
INSTALLATION
Flue and Appliance Fixings
4.13 Position the appliance observing appropriate clearances.
4.14 Apply a bead of suitable weatherproof sealant (silicone or
similar) to perimeter of back face of terminal (see
Diagram 6, A).
AR0606
6
A
4.15 Feed the flue through the wall, making sure it runs
smoothly.
On the inside wall:
4.16 Engage the flue in the inner and outer spigots.
4.17 Make sure rubber seals on the spigots are not damaged
From outside:
4.18 Insert four screws in the flanges of the flue terminal.
4.18 Check sealant has formed a water-tight joint to the wall.
4.19 Any terminal less than 2m above any access (level ground,
balcony or flat roof with access) must be fitted with the
guard supplied (see Diagram 7).
AR0603
7
4. FLUE ASSEMBLY
4.1 Refer to Flue Options in Site Requirements on page 13.
4A. REAR EXIT - HORIZONTAL FLUE
Flue Length
4.2 Measure the total wall thickness and add 65mm.
4.3 The total flue length gives a minimum clearance of 50mm
between the rear of the appliance and the wall.
4.4 Insert the square cardboard sleeve into the flue to support
the inner tube.
4.5 Cut through the flue and sleeve (see Diagram 5).
AR0630a
5
4.6 REMOVE THE CARDBOARD REMNANTS FROM THE
FLUE.
4.7 File the cut edges smooth.
Terminal
On the outside wall:
4.8 Position the flue assembly into the hole. The terminal
should be flat against the wall.
4.9 Make sure the terminal is vertical (see Diagram 5).
4.10 Mark the four fixing holes.
4.11 Remove the terminal to drill the holes.
4.12 Insert wall plugs supplied.
DO NOT FIX THE FLUE AT THIS STAGE.
Kommentare zu diesen Handbüchern